Sprinkler Shield Installation Guide

Racking Safety Wire Installation Manual

Version number 1.0

Date: 27/2/2026

Company: Elan Europe Ltd

Tel: 01925710923

www.elaneurope.co.uk

Overview

This guide explains how to correctly install the Sprinkler Shield system.

Sprinkler Shield provides:

• Visual guidance for better pallet placement near sprinkler heads

• Physical protection and positive feedback to operator to protect sprinkler heads

Correct installation ensures:

• Proper height alignment to sprinkler head.

• Lightly tension wire.

• Secure fixing at both ends

• No interference with sprinkler operation

Product Overview

Sprinkler Shield reduces the risk of:
• Accidental sprinkler head damage
• Water discharge
• Loss of storage capacity
It is particularly suited to racking systems where sprinklers are:
• Not fully protected by flues
• Not shielded by rear beams
• Installed as face sprinklers
The system:
• Acts as a visual guide during pallet put-away
• Provides physical resistance if contacted
• Delivers over 500 kg of push-back resistance under load
Installation uses:
• 3 mm 7×7 wire rope
• 8 mm high-visibility yellow sleeve
• Gripple fixing technology
• Existing bracing holes in racking uprights

What's Included in Your SprinklerShield Kit

Each kit contains:

  • 3 mm wire rope with either 8 mm stud end or carabiner clip (if the wire end you have does not suit your racking please ring 01925 710923 for support)
  • Yellow sleeve (pre-fitted)
  • Small yellow cable ties
  • No.3 Gripple release key
  • 8 mm washer
  • 8 mm serrated flange nut
  • 2 single-arrow yellow level labels
  • 3 double-arrow yellow level labels
  • 200 mm rack-end warning sign
  • Double-sided adhesive pads

Tools and Equipment

Minimum tools:

  • 13 mm spanner (or adjustable spanner)
  • Pair of reasonable scissors.

 

Optional: Before starting:

  • Ensure RAMS and SSOW are in place
  • Close aisles where required
  • Follow site-specific working-at-height procedures

 

Important:

  • Do not cut the wire rope, as the wire ends are fused to prevent fraying
  • Cutting will cause fraying
  • Wear gloves to reduce risk of minor cuts
  • Take care when leaning into racking

Installation

Pre-installation

  • Ensure bracing holes are accessible
  • Confirm stock does not obstruct access
  • Make sure working area is safe and clear

STEP 1 – UNCOIL THE WIRE

  • Thread the end back through the coil
  • Remove twists
  • Ensure sleeve is straight

STEP 2 – FIX THE FIRST END (STUD/CARABINER END)

 

  • Insert stud through appropriate bracing hole
  • Fit washer and flange nut
  • Tighten only one-third to one-half of stud length
  • You need the thread to tension the wire later.
2e4bfb26-4ca2-4f04-a927-d2603925810c
256fdc97-bdec-4e83-b12d-8e96d7909767
8fc902a1-238d-4f14-ba59-add8b773f002

STEP 3 – THREAD THROUGH BAYS

• Move to the next frame

• Pass wire and sleeve through bracing hole

• Repeat across required bays (typically two frames)

• Keep the small yellow cable tie on the sleeve where possible

 
d16dc512-f893-45c4-90b5-2b79424c949c
743da936-c817-488a-99e8-a804a31eaafa
531f8a2b-222c-42ed-98b4-00fd660ac493
280f66e7-64ee-4810-b0ce-197fb49e8b94

STEP 4 – INSTALL THE GRIPPLE

• Slide sleeve back to expose enough bare wire

• Position Gripple close to the racking frame 

• Thread wire through Gripple where marked with the arrow

• Loop through bracing hole(s)

• Feedback through Gripple

• Pull tail end firmly by hand to apply as much tension as possible by hand. You won’t get it tight at this stage, but as much tension here helps later on. 

 

427b9887-9c08-491e-9101-eb13d6199e8a
76653a88-9f9c-4138-ab5f-295bf604d4d3

KEEP THE GRIPPLE LOCK VERY CLOSE TO THE FRAME AT ALL TIMES. 

DON’T SLIDE IT DOWN THE WIRE BUT FEED THE WIRE THROUGH INSTEAD

 THIS ENSURES YOU DON’T HAVE TO REPOSITION THE GRIPPLE LATER

e1b62616-f1db-4472-bcb4-c990701cd9f9
983bceef-b620-4d76-9e67-d30437040c6f
51fe5731-a79b-45ba-aabf-b57198588be1

STEP 5 – APPLY TENSION 

  • Return to the stud end
  • Tighten the flange nut until the wire runs straight across the bays
  • Apply light tension only
  • Do not over-tighten
92ad1e40-e303-4d0c-b3b6-3785b40c8cb0-1
a6fe7eaa-ed01-4bc7-9206-7a92478b83f4-2

STEP 6 – FINISH THE SLEEVE AND TAIL

• Slide sleeve into final position

• Trim sleeve neatly

• Reposition cable tie at sleeve end

• Use additional cable ties to secure excess wire

• Do not cut the wire

 
3f1b2575-1a86-4f26-a90b-d06fc4613680
4fe1a6af-d589-445a-af21-ebea416f4c02
04153757-e92e-4cfa-81fa-43ca0c06256b
29dba111-9811-4425-8deb-db38a235938f
d20a5b17-8c45-4bd7-9e9f-1df925af57e0
ba0190a6-7aee-42d1-bce4-08673c492e67

Level Labels

The kit includes:

• 2 single-arrow labels for the ends of the run

• 3 double-arrow labels for the middle bays

Installation:

• Clean the surface first

• Apply labels to a flat surface

• Avoid beam connectors where possible

Warning Sign:

• Apply adhesive pads to the rear of the sign

• Remove protective liners

• Fix sign to a clean rack frame

• Ensure surface is free from dust

 
f82aeada-c4f5-456a-bccf-455b65d3cc76
8a8d9fd5-3f67-4c70-8473-1ea954165601
b2e5a509-536c-420e-b3a5-8381636d1486

Final Inspections

Check:

If support is required, contact 01925 710923.

Troubleshooting

After 1 week

The wire may stretch slightly after installation.

If slack or slight bowing appears:

  • Tighten the stud end slightly
  • Apply only minor adjustment

Maintenance and Inspection

No routine maintenance required

• Conduct periodic visual inspections

• Replace the system if the wire becomes severely stretched or damaged

In the Event of an Impact

If struck by a forklift truck:
• The wire may stretch
• Re-tensioning may not be possible
• Replacement may be required

Removal Procedure

1. Loosen the flange nut to release tension
2. Attempt to release the Gripple using the release key but this is normally difficult as the gripple has gripped into the wire marking release difficult.

If release is not possible:
Cut the wire between the gripple and the rack frame with wire cutters or snips and remove completely.

Technical Specification

Wire Rope:

• Diameter: 3 mm
• Construction: 7×7
• Breaking strain: over 500 kg (see testing document)

Sleeve:

• 8 mm expandable braided PET
• Self-extinguishing
• Operating temperature range: -50°C to +150°C

Fixings:

• Gripple system
• Hydraulic swaged stud end

Contact and Support